Sparlectra Case Format (SCF)

One self-describing case file (.scf.json): a power-grid-model (PGM) input dataset that a PGM installation reads directly, plus a sparlectra block with what PGM has no model for (slack strategy, tap changers, component names and source ids, state-estimation measurements, study definitions). The framework, the service and the Web UI run it like a MATPOWER or CGMES case. The case's own settings travel in a case configuration file next to it, <stem>.config.yaml.

Use

WriteexportSCF(net; file, ...); write_case_config(file, Dict(...)) for the case configuration file
ReadimportSCF(file); without building the network load_case_config(file), scf_case_config(file), scf_case_studies(file)
Typed formSCFCase with read_scf_json, write_scf_json, build_net, net_to_scfcase; dict entry points scf_to_net, net_to_scf
CLIsparlectra export, with --pgm for the plain PGM dataset
Web UIExport as SCF case file, Export as plain PGM, Save case as, Download selected case on the Case page (Web UI)
Fixturesdata/scf/sp_casePST.scf.json, the permanent version 1 file every future reader must keep loading unchanged; data/scf/pgm_interop.json, a file as power-grid-model writes it

Writing a case file

exportSCF writes a network as one JSON file that reads back machine-exact, with its source, the intended calculations and, on request, the solved start state; the Web UI offers the same export from the Case page.

using Sparlectra

net = createNetFromMatPowerFile(filename = "case118.m")
exportSCF(net; file = "case118.scf.json",
          source_format = "matpower", source_reference = "case118.m",
          intended_calculations = ["power_flow", "state_estimation"])
write_case_config("case118.scf.json", Dict("power_flow.mode" => "auto"))

The Web UI export picks up a <case>.measurements.csv next to the case and stores the form's overrides in the case configuration file; Save case as writes the same set under a new name (Save case as).

Reading a case file

net = importSCF("case118.scf.json")
runpf!(net, 30, 1e-8, 0)

The reader builds the network through the public constructors (addBus!, addPIModelACLine!, addPIModelTrafo!, addProsumer!, addShunt!, addLink!) and ends with validate!. It refuses unknown top-level keys, unknown keys inside sparlectra and unsupported component types by name, and requires unique ids and resolvable from_node, node, measured_object, regulated_object, branch and star_node references of the right kind. load_case_config(file), scf_case_config(file) and scf_case_studies(file) return the case configuration file, the deprecated in-file block and the study definitions without building the network.

Configuration precedence

A case that ships a <stem>.config.yaml computes the same numbers on every installation: its case-scope keys resolve from explicit config_overrides (API, CLI, Web UI form), then the case configuration file, then the packaged defaults; the machine's YAML supplies machine-scope keys only (Merge precedence). effective_config.yaml of each run records what took effect.

Case-scope keys are the keys of GUI_EDITABLE_CONFIG_KEYS in matpower_import.*, cgmes_import.*, powsybl_import.*, power_flow.*, state_estimation.*, short_circuit.* and qsts.*; output.*, benchmark.*, runtime.*, webui.* and matpower_export.* stay in the machine configuration (scf_is_case_config_key(key) answers per key). A key outside the case scope is refused by name on read. The in-file block sparlectra.config is deprecated: the writer does not emit it, the reader applies it below the case configuration file with a warning naming the new place. The Web UI form is seeded from the case file and posts every option as an explicit override (Case-specific settings).

The reference: single, distributed, or a source

roles.slack states which reference the case was built with:

modeMeaning
singleone ideal slack per island, nodes lists them
distributedthe reference bus keeps the angle, the island's active-power imbalance is shared; participation carries one factor per generator
sourceno slack flag at all: the in-service PGM source components are the reference (this is what a file written by power-grid-model looks like)
"roles": {
  "slack": {
    "mode": "distributed",
    "nodes": [1],
    "normalize": true,
    "participation": [{"object": 23, "factor": 2.0}]
  }
}

The factors are the network's own participation factors (MATPOWER APF, CGMES normalPF). They travel with the model but do not switch the feature on; the case has to ask for it in its configuration (these keys, in <stem>.config.yaml or in the deprecated in-file block shown here):

"config": {
  "power_flow.distributed_slack.enabled": true,
  "power_flow.distributed_slack.p_mode": "imported"
}

imported reads exactly those factors; explicit weights (power_flow.distributed_slack.weights) are a run setting and stay in the YAML configuration (Power-Flow Configuration).

extra.<appliance>.reference_pri flags the appliance that holds the reference. extra.<appliance>.reference_priority says which one takes it over when an island has none or the slack is lost in N-1: an integer with the CGMES semantics (1 is the strongest, larger is weaker), written only where one is stated; a file without it reads with no priority on any unit (Reference priority).

Generator costs from a MATPOWER case (mpc.gencost) sit on their machine as extra.<machine>.gencost: {"p": [...], "q": [...]}, each a MATPOWER cost row (MODEL, STARTUP, SHUTDOWN, NCOST, then points or coefficients), q optional. No calculation reads them; a MATPOWER export writes the block back unchanged (Generator costs).

Dynamic unit data

Since revision 1.3 a machine can carry its DynamicData as extra.<machine>.dynamics, one key per field under the field name. A field at nothing is left out, the fields with a numeric default are written with their value, unit_type is "synchronous", "grid_following" or "grid_forming":

"dynamics": {"inertia_s": 4.25, "damping_pu": 0.0, "droop_pu": 0.05,
             "deadband_hz": 0.0, "primary_reserve_mw": 0.0,
             "agc_participation": 0.0, "secondary_reserve_mw": 0.0,
             "unit_type": "synchronous", "black_start": false}

A machine without dynamic data has no block, and a case without any writes the bytes it wrote before. On read a missing key takes the default of Dynamic Unit Data, a missing unit_type follows the inertia. An unknown key, a value of the wrong type or a value against the rules of its field fails with an ArgumentError naming the machine and the key. Write and read keep every value bit for bit. No calculation reads the block.

Importers and the typed case

Every importer builds its network directly (an SCF file through build_net); converting a case into an SCF file is always an explicit export, so imported values stay bit-exact.

SCFCase is the in-memory form of one document (the PGM data section as typed component vectors, the sparlectra block as sub-objects). read_scf_json(path) parses and validates a file into it, write_scf_json(case, path) serializes it to the canonical bytes, build_net(case) constructs the network and applies the run configuration's net parameters exactly once, net_to_scfcase(net) is the export direction (same keywords as exportSCF). importSCF and exportSCF wrap these four; scf_to_net/net_to_scf keep the dict entry points.

The round trip

A network written by Sparlectra, read back and written again gives two byte-identical files: bus and branch order, the source system's bus numbers, tap ratios, shunt susceptances with their sign, controllers, measurements and the power-flow result come back bit for bit, and a run on the re-read network gives the same power-flow iterations and voltages and the same state-estimation objective, degrees of freedom and state. A network imported from MATPOWER, CGMES or DTF keeps its electrical model and solution, not every detail of the source file (CGMES mRIDs are recorded, MATPOWER comments and column layout are not).

Notes

  • Per-unit values can land one ulp away when no exact SI preimage exists; the Y-bus deviation is at the 1e-16 level.
  • Tap regulation bands snap to the step grid: the operating tap ratio is exact, a band edge can move by less than one step. A neutral ratio outside its own band is kept and named in a warning on load. On case13659pegase one phase-tap band moves by one step on the second write; the third write equals the second.
  • An unlimited branch rating (MATPOWER rateA = 0, arriving as Inf) is absent from the PGM dataset (no i_n is no limit there) and travels as "inf" in the namespaced block; any other non-finite number is a hard error naming the key.
  • An unlimited reactive band is stated by absence: max_q_mvar and min_q_mvar are written only when finite, in both blocks; a missing and an infinite limit give the same power flow.
  • Impedances are written from the base (physical) values; exporting a FACTS-compensated operating point is a hard error naming restoreBaseImpedances!.

The operating point travels in extra: the reactive band of every machine, its voltage setpoint and whether it regulates (max_q_mvar, min_q_mvar, vm_pu, regulated), because a machine written as a PGM source has no voltage_regulator row. So does a voltage-dependent controller: extra.<machine>.qu_control and pu_control carry the characteristic's points in per unit (voltage, power on meta.s_base), its interpolation mode and its limits in MVAr / MW:

"qu_control": {
  "points": [[0.95, 0.30], [1.00, 0.00], [1.05, -0.20]],
  "interpolation": "spline",
  "qmin_mvar": -50.0,
  "qmax_mvar": 50.0
}

interpolation is linear, spline or polynomial (Voltage-dependent control); the reader validates at least two points, strictly increasing voltages, a known mode and qmin_mvar not above qmax_mvar. The MATPOWER converter's constant controllers keep their short form, the flag pq_gen_controller; an explicit qu_control/pu_control object wins over it. A setpoint alone does not promote a machine: the reader restores the regulated flag the file states.

Ids are deterministic: the writer walks the components in a fixed type order and, inside a type, in lexicographic name order, so the same network, or a case rebuilt from its source, gets the same ids. extra records each element's internal index, and measurements.rows lists the measurements in their internal order, because internal order fixes generated ids and summation order. The writer emits the SI value that reads back into exactly the per-unit value it started from (both sides derive the impedance base from u_rated and s_base with the same formula); measurements.rows carries the sigma of each measurement (one PGM sensor sigma cannot express a P and a Q sigma) and a value only where the SI value would not read back exactly. Floats use the shortest round-trip representation; the file is pretty-printed with one key per line (lists of plain scalars inline), so a diff points at the changed field.

Fields that are not written

A field whose value equals its documented default is left out and the reader puts it back; this applies to the namespaced block only, data keeps every attribute PGM requires.

FieldDefaultMeaning when absent
extra.<branch>.kind"BranchC"an ordinary line
extra.<machine>.vm_puabsentthe machine does not regulate (a regulating one keeps its setpoint in its voltage_regulator row, the reference in source.u_ref)
extra.<machine>.max_q_mvar, min_q_mvarabsentno reactive limit
extra.<machine>.max_p_mw, min_p_mwabsentno active limit
extra.<machine>.qu_control.interpolation, pu_control.interpolation"linear"piecewise linear characteristic
extra.<machine>.qu_control.qmin_mvar, qmax_mvar, pu_control.pmin_mw, pmax_mwabsentno limit on the controlled value
extra.<machine>.regulated, apu_nodefalse
extra.<machine>.reference_priority0no reference priority stated
extra.<machine>.gencostabsentno generator cost data
extra.<machine>.dynamicsabsentno dynamic data (ProSumer.dynamics = nothing)
extra.<branch>.meta.sn_mvaabsentno rating recorded
components.tap_changer[].tap_est_mode"none"the tap is not released for estimation
components.tap_changer[].controllers[].posabsentthe step was not transferred: the changer sits at its middle position, the neutral position 0, and the import names it in an info line
tap_changer_models.<id>.ratio.step, .phase.step, .estimation.changers[].stepabsentthe changer sits at its middle position, neutral_step (neutral in estimation), named in an info line
components.tap_changer[].controllers[].step_assumed, tap_changer_models.<id>.ratio.step_assumed, .phase.step_assumed, .estimation.changers[].step_assumedfalsepos or step is a step of the source. The writer puts true on a changer whose step was not transferred: pos or step then holds the assumed middle position, and the reader marks the changer again and names it in an info line, so a written middle position never reads back as a real step. A tap controller or a QSTS carry that moves the changer takes the mark off, the step it reaches is a step
components.tap_changer[].controllers[].grid"fraction"ratio positions on the fraction grid ratio_base / (1 + pos * step); "linear" for a CGMES changer
components.tap_changer[].controllers[].declaredtruethe changer is nameplate data; a declared phase changer joins the mass release of the tap estimation. The writer puts false on a controller no nameplate row declared (the default ratio or phase grid of a transformer), so the re-read keeps that state
components.transformer3w[].status1in service
roles.slack.normalizetrueparticipation factors are normalized

area and zone are not in this list (their constructor value is "unknown", not 1) and are written only when set.

Areas and zones

extra.<node>.area and extra.<node>.zone are integers: the bus's area and loss zone, from the MATPOWER bus table (columns BUS_AREA and ZONE) or set with addBus!(area = ...). A bus without one has no key. The reader restores both onto the bus. The multi-area state estimation takes its partition from area (see Multi-area estimation).

The names of the areas, where the source has them (the operator models or regions of a CGMES import, Bus areas), go to the block sparlectra.areas, area number => name; a file without names has no block:

"areas": { "1": "http://nord.example/sparlectra", "2": "http://sued.example/sparlectra" }

File layout

The root object is the PGM root object with exactly one added key:

{
  "version": "1.0",
  "type": "input",
  "is_batch": false,
  "attributes": {},
  "data": { },
  "sparlectra": { }
}

data is a valid PGM input dataset in SI units (V, W, var, VA, ohm, siemens, farad, ampere, radian); sparlectra holds everything PGM has no model for. A plain PGM reader still gets a computable network; see Interoperability for what it loses.

The PGM subset in data

ComponentSparlectra elementNotes
nodebusu_rated is the rated line-to-line voltage in V
lineline, cabler1, x1 in ohm, c1 in farad, tan1, i_n in A; a shunt conductance rides in tan1 (= g/b), and the one value that encoding cannot spell, g without capacitance (b = 0), is written as a direct g1 in siemens, an SCF extension the strict PGM writer strips by name
generic_branchtransformer, phase shifterr1, x1, g1, b1 referenced to the to side, k the live off-nominal ratio, theta the live shift in radians, sn in VA
linkbusbar couplerzero-impedance connection
sourceexternal network injectionu_ref, optional u_ref_angle
sym_load, sym_genload, generatorp_specified in W, q_specified in var
shuntshuntg1, b1 in siemens
voltage_regulatorPV control of a generatoru_ref in per-unit, q_min/q_max in var (PGM 1.13 or newer)
sym_voltage_sensor, sym_power_sensor, sym_current_sensorstate-estimation measurementsvalues and sigmas in SI

The Sparlectra Y-bus stamps the tap on the from side, so r_pu/x_pu are referenced to the to side, like PGM's generic_branch.

Unit system

The numbers in data are base SI units:

Field groupFieldsUnit
line impedanceline.r1, line.x1ohm
line capacitanceline.c1farad
line loss factorline.tan1 (conductance over susceptance)1
line conductance without capacitanceline.g1 (optional)siemens
conductance, susceptanceg1, b1 of generic_branch and shuntsiemens
powerp_specified, q_specifiedW, var
voltage basenode.u_ratedV (line to line)
current ratingline.i_nA
power ratinggeneric_branch.sn, meta.s_baseVA
anglethetarad

sparlectra.meta.units declares in which unit system the branch and shunt parameters are stated. Two values exist:

  • "si": the values in data are the ones the network is built from. This is what a file without the key means, so every file written before the key existed reads unchanged.
  • "pu": the impedances and admittances are stated per unit in a pu block of the component's extra entry, and the network is built from them. The data section stays a complete SI view for PGM readers.

A pu block holds r_pu, x_pu, b_pu, g_pu for a line or generic_branch (total shunt values, on the base of the to node) and g_pu, b_pu for a shunt. The base is the one the file already carries: meta.s_base and the u_rated of the node; a "pu" file without meta.s_base or with a node without a positive u_rated is an ArgumentError naming the field, and so is a branch or shunt without its pu block. Powers, voltages, ratings and angles stay in SI in both systems. Powers and voltages convert by a power of ten and read back exactly. Ratings and phase-shift angles do not always: a line rating travels as i_n in A, a transformer rating as sn in VA, a shift as theta in rad, and a rating like 200 MVA can read back as 200.00000000000003 MVA, a shift like -0.06138 degrees as -0.06137999999999999 degrees. The difference is in the last bit only.

The declaration exists because a per-unit value converted to ohm and back does not always return the same number: in about one value in ten no SI value maps back exactly. A case that comes from per-unit data therefore keeps it per unit, and the only conversion happens when the network is built.

An SI file (excerpt, node 2 rated 110 kV, 100 MVA base, 50 Hz):

"data": { "line": [ { "id": 7, "from_node": 1, "to_node": 2, "r1": 1.2342, "x1": 3.0976, "c1": 1.1312e-7 } ] },
"sparlectra": { "meta": { "s_base": 100000000.0 } }

The same line in a "pu" file:

"data": { "line": [ { "id": 7, "from_node": 1, "to_node": 2, "r1": 1.2342, "x1": 3.0976, "c1": 1.1312e-7 } ] },
"sparlectra": {
  "meta": { "s_base": 100000000.0, "units": "pu" },
  "extra": { "7": { "name": "ACL_1", "pu": { "r_pu": 0.0102, "x_pu": 0.0256, "b_pu": 0.0043, "g_pu": 0.0 } } }
}

exportSCF writes SI by default and "pu" with units = :pu; the MATPOWER adapter (convert_case) and the Web UI export of a MATPOWER case write "pu". A strict PGM file (strict_pgm = true) has no sparlectra block and is always SI.

The sparlectra block

KeyContent
format_versionschema version of the block (1.3)
metacase name, s_base in VA, units ("si" or "pu", see Unit system), f_nom (system frequency in Hz, optional; the writer always states the frequency of the net; on read it sets the frequency of the net and wins over model.nominal_frequency_hz, which applies only when f_nom is absent, default 50 Hz; a value that is not a positive number is an ArgumentError naming meta.f_nom; see System frequency), source format and reference, producer, intended_calculations as the file's contract, and for a CGMES delivery cgmes_ids, the mRID registry of the import keyed by structural identity, which the reader restores so a re-export keeps the mRIDs
roleswhat PGM cannot express: slack.mode (single, distributed, source) with its nodes or participation factors, auxiliary nodes, isolated nodes
extraper-component annotations keyed by id: name (the reference name every other section resolves against), external_id (CGMES mRID, MATPOWER index), bus/branch index, node type, ratings, and in a "pu" file the pu block of each branch and shunt
components.tap_changerthe tap changers PGM has no model for: per controller the step grid, position, band, and nameplate angle, plus the neutral ratio and angle. Ratio positions count on the fraction grid ratio_base / (1 + pos * step) (nameplate data), or with grid: "linear" on the grid of a CGMES changer, ratio_base + pos * step. step_assumed: true marks a position that was not transferred and is the assumed middle position
components.transformer3wthree-winding transformer: either the grouping of three existing generic_branch legs (their star node, and which end is hv/mv/lv; the electrical values stay in the legs and are never duplicated) or a nameplate that describes the transformer directly, see below
components.sc_sourceIEC 60909 source data (external network injections, machines) that PGM's source cannot carry beyond sk/rx_ratio
components.shunt_statewhat PGM's g1/b1 cannot say: whether a shunt is in service, whether it is a voltage-dependent injection rather than an admittance, and whether its susceptance is released as a state-estimation state. Only deviating shunts produce a row
transformer_typesnamed transformer nameplates in CGMES PowerTransformerEnd vocabulary, referenced by components.transformer3w entries
branch_shunt_splitper branch id, only for a branch whose two terminal shunt arms differ: g_from_pu, b_from_pu, g_to_pu, b_to_pu in pu on the branch base. The data section keeps the PGM totals (c1, b1); on load the row overrides the symmetric half. Absent block: symmetric
tap_changer_modelsper branch id, the typed tap-changer models of the from-side winding: ratio (the PowerTransformerTaps inputs: vn_kv, step, low_step, high_step, neutral_step, voltage_increment_kv, neutral_u_kv, convention, step_assumed), phase (kind symmetrical, asymmetrical or tabular, the steps, voltage_step_increment, step_phase_shift_increment, winding_connection_angle_deg, x_min, x_max, convention, step_assumed, and table rows step, ratio, angle_deg, x_pu for tabular), tap_changer_model when the impedance correction is on, and base_ratio, base_shift_deg, the winding ratio and shift the models move from (k and theta of the data row carry the steps). On load the models are restored onto the winding and the resolver derives ratio, shift and grid from them; an entry without base_ratio or base_shift_deg takes k or theta as the base; components.tap_changer rows still describe the grid for readers that know no model. The older spelling extra[<id>].phase_taps is still read, with a warning. The optional key estimation carries the tap changer set the state estimation uses for the branch, as an import that knows the changers stored it (CGMES): origin (cgmes or powsybl, any other value is refused on write and read), ratio_n, shift_n_deg and the changers with name, mrid, kind, role, side, neutral, low, high, step, impedance and, where set, additive, du, alpha_deg, dphi_deg, step_abs, outside_du, rx_correction, step_assumed, x_curve (x_min, x_max, a_max_deg, form) and table rows (step, ratio, angle_deg, r, x, g, b). An empty changers list means the transformer has no tap changer. An entry with only this key runs no resolver; a file without it reads as before
components.controllersFACTS and regulation, in the declarative control.controllers schema verbatim: same type names, same keyword names. The reader hands the entries to applyConfiguredControllers!, so there is one construction path. The shunt of a shunt voltage controller is not written as a shunt row; its entry carries the present susceptance as bs_start_mvar and, where they deviate, the shunt's status, model and estimate in a shunt_state object with the keys of a components.shunt_state row
contingenciesremoved in 0.40.0. A file that still carries the block fails on load with a message naming the scenarios block and the Web UI scenario editor
scenariosthe scenario model: mode (explicit, n1_branches, n1_generators, n1_all), exclusions, events (correlated event classes generated next to the list: double_circuits, busbars, substations, links, name_groups, pairs), and the ordered scenario list, each scenario name, weight, an optional kind (written when it is not explicit) and its ops (op = status/set/scale, target component class, id the SCF component id, plus value, field, factor as the op needs). The N-1 modes and the event classes expand through the same generators runContingencies! uses (N-1 Contingency Analysis); a scenario of status-0 ops only runs as one outage event
short_circuitIEC 60909 study definition: case (max/min), optional c_factor, sweep (all_buses/explicit) and, for an explicit sweep, the buses list of node ids
measurements.rowsone row per measured value with the semantics of the measurement table, in the order of the measurement vector; see Measurements
configcase-specific dotted configuration keys (same allowlist the API and Web UI use); deprecated in favour of the case configuration file
start_stateopt-in bus voltages as start values, never as results

The study blocks are validated on load (an unknown mode, an out-of-band c_factor or an empty outage list fails on read, not at the start of a long sweep).

The two blocks for one transformer branch with id 12:

"branch_shunt_split": {
  "12": {"g_from_pu": 0.0004, "b_from_pu": -0.012, "g_to_pu": 0.0, "b_to_pu": 0.0}
},
"tap_changer_models": {
  "12": {
    "phase": {"kind": "asymmetrical", "step": 3, "low_step": -10, "high_step": 10,
              "neutral_step": 0, "voltage_step_increment": 0.01,
              "winding_connection_angle_deg": 90.0, "convention": "reciprocal_from_side"}
  }
}

The data section stays a valid power-grid-model dataset: the split and the models live only in the sparlectra block, and exportSCF(strict_pgm = true) names both among what the plain dataset does not carry.

Names and source ids

extra[<id>].name is the reference name that measurements, controllers, contingencies and reports resolve against (Sparlectra's bus dictionary key); a differing internal component name travels as component_name, the source-system id as external_id (for a CGMES delivery the mRID, marked source_id_kind: cgmes_mrid, otherwise the internal component id). With "name": "Ostheim_110", "external_id": "H1" the import uses the place name everywhere, restores external_id and component_name onto the network, and a re-export preserves both byte for byte, as the shipped demo cases do. Branches, links, appliances and shunts take name and external_id as their component name and id in the same way, so results, measurement tables and contingency rows show the names of the file (Lindhof_110_20, not the generated B_2WT_110_4_5). A generic_branch without a tap_changer row has no tap changer.

Three-winding transformers without writing legs

Instead of three hand-written generic_branch legs plus a star node, a transformer3w entry may describe the transformer as CGMES does: one PowerTransformerEnd per winding with rated_u, rated_s, r, x and b. The reader builds the star equivalent through add3WTPiModelTrafo! and creates the auxiliary star node itself.

"sparlectra": {
  "transformer_types": {
    "cgmes_220_110_10_100MVA": {
      "ends": [
        {"role": "hv", "rated_u": 220000.0, "rated_s": 100000000.0, "r": 0.6, "x": 30.0, "b": 0.0},
        {"role": "mv", "rated_u": 110000.0, "rated_s": 100000000.0, "r": 0.4, "x": 15.0, "b": 0.0},
        {"role": "lv", "rated_u": 10500.0,  "rated_s": 40000000.0,  "r": 0.2, "x": 8.0,  "b": 0.0}
      ]
    }
  },
  "components": {
    "transformer3w": [
      {"id": 7, "type": "cgmes_220_110_10_100MVA",
       "nodes": [{"role": "hv", "node": 1}, {"role": "mv", "node": 2}, {"role": "lv", "node": 3}]}
    ]
  }
}

A type entry is a named nameplate shared by transformers of one design; an entry can also carry its nameplate inline. An entry either points at legs or describes them; mixing the two fails on load.

Which CIM attributes the nameplate speaks

One nameplate end is one CIM PowerTransformerEnd:

Nameplate keyCIM attributeUnit here
rolethe winding's voltage level (CIM orders ends by PowerTransformerEnd.endNumber)hv, mv, lvrequired
nodethe end's Terminal to TopologicalNodenode idrequired, in the end or in nodes
rated_uPowerTransformerEnd.ratedUVrequired
rated_sPowerTransformerEnd.ratedSVArequired
rPowerTransformerEnd.rohmrequired
xPowerTransformerEnd.xohmrequired
bPowerTransformerEnd.bsiemensoptional, default 0
status (on the group, not the end)in service0 or 1optional, default 1

All three ends state r, x and b on the HV base, the star-equivalent form the CGMES import produces; the reader converts to per unit with the highest rated_u as the voltage base. Not taken from CIM: the magnetising conductance g (the losses sit in r), phaseAngleClock and connectionKind (the vector group, not evaluated by the balanced positive-sequence model), and the tap changers. A RatioTapChanger or PhaseTapChanger lives in its own components.tap_changer entry, referenced by the group's tap_changer; controller index 1 is the ratio changer, index 2 the phase changer, each with step size, live position and position band. Any other nameplate key fails on load. The nameplate is an input shorthand: an export always writes the explicit legs plus the grouping, the form that round-trips.

What the star equivalent is called

The reader generates the names of the star point and the three legs, and whatever addresses them later (a contingency case, a measurement, a tap block) uses exactly these:

ObjectNameBuilt from
star nodeAux3WT_<hv>_<mv>_<lv>the three terminal bus names
legB_2WT_<Vn>_<star>_<terminal>rated voltage in kV, then the two bus indices

For the nameplate above, with terminals HV, MV and LV, the export writes the star node Aux3WT_HV_MV_LV (listed under roles.aux_nodes) and the legs B_2WT_220_4_1, B_2WT_220_4_2 and B_2WT_220_4_3; the grouping states which leg is which end:

"components": {
  "transformer3w": [
    {"id": 13, "star_node": 1, "leg_direction": "star_to_terminal", "tap_changer": 10,
     "ends": [
       {"role": "hv", "branch": 5, "terminal_node": 2, "u_rated": 220000.0, "sn": 100000000.0},
       {"role": "mv", "branch": 6, "terminal_node": 4, "u_rated": 110000.0, "sn": 100000000.0},
       {"role": "lv", "branch": 7, "terminal_node": 3, "u_rated": 10500.0,  "sn": 40000000.0}
     ]}
  ]
}

leg_direction says that every leg runs from the star node to its terminal (terminal_to_star for the reverse, mixed when the legs differ, as for a CGMES leg with a tap changer), and the roles follow the terminal voltages, highest first. A CGMES delivery keeps its own names from the PowerTransformer and its ends; the generated names appear only for a nameplate-built transformer.

Running the studies

A study run on a case file executes what the file defines and applies the file's own configuration.

StudyFile blockEntryResult
N-1 and scenariosscenarios (a scenario may combine several status, setpoint and scaling operations, so a double outage is one scenario)runScenarios!; the service with scenario_source = file_block; the Web UI's scenario editor writes the blockthe per-scenario weight is honored, run.log records where the case list came from
State estimationmeasurementsthe run needs no separate CSV; an explicitly picked CSV winsmeasurements.csv is still written as the run's artifact
Short circuitshort_circuit: case (max or min), optional c_factor, the sweepsweep: explicit takes a buses list of node ids resolved through extra; without an explicit sweep PGM's own data.fault rows name the faulted nodeboth cases are always evaluated (short_circuit_max.csv, short_circuit_min.csv); case only decides where the headline numbers come from

Notes

  • Scenarios are a feature of this format. Converting a case to MATPOWER, CGMES or PowSyBl does not carry the scenarios block.
  • An unknown bus id in an explicit sweep fails the run; a fault_type other than three_phase or a non-zero r_f/x_f is refused on load (balanced bolted fault only). The file's c_factor applies at the configuration default and loses against an explicit short_circuit.c_factor.
  • Source data is in components.sc_source (empty fields are written as null). A machine without a source row enters with the default reactance, the rows it feeds are flagged and the run ends with status warning; a file whose sources carry neither data nor a rated power is refused (Short-Circuit Analysis). The reference unit of a bus with a feeder row is that feeder, not counted twice. An export writes the rows of the file only.

Source formats

The writer serializes a Net, so every imported case exports the same way, with the payload its importer put into the network.

SourceWhat the file carries
MATPOWERbranch and shunt parameters per unit (meta.units = "pu") when written by the Web UI export or convert_case, bus and branch names, the mpc.sparlectra extensions (tap-changer nameplates as components.tap_changer, busbar couplers as data.link), branch kinds, ratings
CGMESmRIDs as external_id, the three-winding star grouping with its auxiliary node, IEC 60909 source data, the reference names of the topological nodes
DTFstation reference names, transformer tap data, ratings

Three-winding transformers need no conversion: the star equivalent (three legs plus an auxiliary star node) is what PGM documents for generic_branch; the grouping block only records which legs belong together.

Measurements

The measurements of a case travel twice: as PGM sensors in data, in SI, for a PGM reader, and as sparlectra.measurements.rows with the semantics of the measurement table, which Sparlectra reads.

PGM sensors: a bus voltage (plus its angle if present) becomes one sym_voltage_sensor, a bus balance P/Q pair one sym_power_sensor with measured_terminal_type = node, a branch-end P/Q pair one branch power sensor, a current magnitude/angle pair one sym_current_sensor (magnitude and sigma in A); a missing half of a pair is null. The shunt bay has no PGM sensor.

measurements.rows holds one entry per measured value, in the order of the measurement vector (the WLS objective sums in that order):

KeyContent
typeU, P, Q, Va at a node; P, Q, I, Ia at a terminal
nodenode id: U, Va, and P/Q as the bus balance (injection positive)
terminal{"branch": id, "side": "from"} (or "to") for a branch end; {"shunt_bay": node id} for the shunt bay of a node: Q is the sum over its shunts, I and Ia the bay current
sensorthe PGM sensor that carries the reading; absent for a shunt-bay row
idthe Sparlectra measurement id; absent when it equals the default id of its location, which the reader restores: Vm_bus_<k>, Pflow_branch_<k>_from and so on, where k is the bus or branch number inside Sparlectra (the index recorded in extra), not the node or branch id of the file
valuein kV (U), MW, MVAr, A or degrees; written only where the sensor value would not read back bit for bit, and always for a shunt-bay row
sigmain the same unit
validfalse for an inactive measurement; absent means true
zero_injectiontrue for a zero-injection row (a P or Q balance at a node, the source token zero_injection of the table); absent means false. From 1.2 on the id decides nothing; a 1.0 file marks such a row only by the id ZI_PINJ_bus_<k> / ZI_QINJ_bus_<k> with value 0, and the reader keeps that rule for 1.0
originwhere the value comes from (pseudo, derived, pseudo_restore, last_value, range_check, see Measurement); absent means measured, a meter reading. Written since Sparlectra 1.1.1

Units carry no base, as in the table: only U is divided by the rated voltage of the node (u_rated / 1000) on reading. A U value or sigma that no 64-bit float divides back to its per-unit value is written with up to 18 significant digits. The reader keeps the text of value and sigma in measurements.rows only, and divides such a U text at 256 bits, as the table does; every other number of the file is read as a 64-bit float. A row without value or sigma takes it from its sensor; a sensor no row names is read after the rows with the id Vm_<node id> (Pinj_<node id>, Imag_<branch id>, ... with the ids of the file). A bus link flow has no row: the file has no sensor for a bus link, and the export names such rows in a warning (the measurement table carries them on the terminals of the link).

Two places where the block differs from the table: it is keyed by the ids of the file instead of names or mRIDs, and the shunt bay is keyed by its node (the measurement is the sum over the shunts of the bus) and also carries a current angle Ia, which the table has no place for. Provenance, noise, file formats and generators: Measurements.

Interoperability

LevelWhat you get
PGM-readablethe data section alone is a valid PGM input dataset
Sparlectra-completethe full file: slack strategy, tap changers, names, measurement detail, configuration
Lossy toward PGMa PGM reader loses the tap changer detail (the live ratio survives in k/theta), the slack strategy (it sees source components), the names, and the configuration
Strict PGMexportSCF(net; strict_pgm = true), the "Export as plain PGM" button, or sparlectra export --pgm writes the dataset alone, for a consumer that reads PGM and nothing else

Strict mode drops the namespaced block, names what it dropped in a warning (always f_nom: PGM has no frequency field, the line c1 is written with the frequency of the net, and a reader of the file takes model.nominal_frequency_hz), and rewrites a slack generator as a PGM source (PGM's reference is a source; a generator left in place would make the node inject twice).

A file written by power-grid-model has no sparlectra block; its in-service source components become the reference, and since PGM's source is Sparlectra's external network injection, a case that arrives with a source leaves with a source. Its sk and rx_ratio are read as feeder data, so a short circuit runs on the file as it stands, and power_flow.external_grid with source: auto (Power-Flow Configuration) moves the reference behind $z = U_n^2 / S_k''$ and reproduces what PGM computes; the default stays the ideal slack. An export writes sk/rx_ratio back whenever the network carries them. Its sym_current_sensor rows are read in A, as PGM defines them (i_measured = 50.0 is 50 A); before 0.50.0 Sparlectra divided them by 1000.

Time series

A time series on a case file is a zip with the unchanged case, a manifest and one table of patch operations for all steps; see SCF time series. The case file has no series block.

Version and compatibility

sparlectra.format_version is always written with the current revision. A reader accepts its own and the older revisions listed below. Backward compatibility across revisions is not promised: a breaking change is named in the changelog; a case file is an exchange and archive format for the version that wrote it.

SCF revisionReader behaviour
1.3the current revision: accepted, written by every export. Adds the optional block extra.<machine>.dynamics (Dynamic unit data)
1.2accepted and read as written: it differs from 1.3 only by the missing dynamics block. Current sensors carry A, measurements.rows follows the measurement table
1.0accepted; its i_measured and i_sigma are 1000 times too large and are divided by 1000 on reading, giving the value that was exported; its measurements.rows (one entry per sensor with sparlectra_ids, sigmas, positions) and measurements.shunt_bay_rows are read as before
1.1the pre-release name of 1.0: read as 1.0 with an info message asking for a re-export
any other valuerefused by name, stating what it found, what it expected, and that the case has to be re-exported
field absentrefused the same way; a dataset written by power-grid-model has no namespaced block and skips the check