Generic Control Framework
runpf! is the inner numerical solver; run_control! runs controller-driven outer iterations around repeated power-flow solves, and run_sparlectra dispatches through it whenever collect_outer_controllers(net) returns a controller. Built-in controllers: PowerTransformerControl (tap changers: voltage, active power, combined; theory below), MachineVoltageControl (Remote Voltage Control), ShuntVoltageControl (SVC, and MSC/MSR switched banks via step_mvar), SeriesReactanceControl (TCSC, and SSSC via v_inj_max_pu) and HvdcPairControl (back-to-back HVDC pairs).
Architecture
run_sparlectra (public entry)
|
v
collect_outer_controllers(net)
|
v
run_control!
|
+--> runpf!
+--> control_evaluate!
+--> control_propose_update!
+--> control_apply_update!
+--> runpf! again
|
v
ControlRunResult stored on net.control_resultPublic entries (run_acpflow is an alias; both return SparlectraRunResult):
run_sparlectra(; net = net, ...)
run_sparlectra(; casefile = "case14.m", path = "...", ...)Use
| Layer | Function | Purpose |
|---|---|---|
| Framework | run_sparlectra (run_acpflow alias) | Import, configuration, control, solve, output |
| Solver | runpf! | Solve a built Net with a PowerFlowConfig |
| Control | run_control! | Execute the outer-loop controllers; run_control!(net; controllers = [...]) runs user-defined ones |
| Configuration | control.controllers, control.max_outer_iterations | Declarative controllers, global outer-loop budget (Configuration) |
| Result | latest_control_result(net), net.control_result, controllableElements(net) | The ControlRunResult of the last run and the generic element records |
ControlRunResult fields | status, converged, outer_iterations, powerflow_solves, last_pf_iterations, total_pf_iterations (sum over all passes; the result header reports the last pass and this total), last_pf_status, controllers, trace, elements | Terminal status: :no_controllers, :disabled, :no_active_controllers, :pf_failed, :converged, :blocked (a pass in which no controller moved; one closing solve at the final controller state follows and counts in both totals), :max_outer_iterations |
| Trace rows (transformer control) | outer_iteration, controller_name, controller_type, transformer_id, mode, status, converged, at_limit, achieved_vm_pu, target_vm_pu, achieved_p_mw, target_p_mw, tap_ratio, phase_shift_deg | One row per controller and outer iteration in which it acted; a controller held back by its priority writes none |
Element record (controllableElements) | name, element, device, actuator, actuator_min/actuator_max, quantity, target, target_value, discrete, enabled, live status/converged/at_limit | ControlRunResult.elements stores the same records at run end |
| Framework result | SparlectraRunResult.numerical_converged (the last PF solve only), solution_available (that solve is usable), final_converged (converged PF solve, passed limit validation, control_status :none or :converged) | :blocked, :max_outer_iterations and other non-success states keep the last usable solution without counting as framework convergence |
| Legacy boundary | erg reflects inner PF success only: :pf_failed maps to erg = 1 | :blocked or :max_outer_iterations are not PF failures |
A user-defined controller subtypes AbstractOuterController (with AbstractControlState and AbstractControlUpdate) and implements the hook methods of run_control! from the Controllers Reference; its own outer-loop limit combines with the global budget control.max_outer_iterations.
Declarative controllers in configuration
Under control.controllers each named mapping declares one controller: type selects the device function, the remaining keys mirror its keyword arguments. The run pipeline applies the declarations before the outer loop; applyConfiguredControllers! does the same for a programmatically built net. Schema, types and validation: Configuration. An element that already carries a controller of the declared type is skipped, so repeated runs do not stack duplicates (a transformer counts per actuator: entries on its ratio and on its phase tap are two controllers); to change it, rebuild the net or adjust it programmatically. There is no generic addController!: attachment is device-specific (transformer controllers live on the winding in side.controls, the others in net.machineControls), and the add*Control! functions carry the reference resolution and exclusivity checks.
Controller priority
Every controller takes an integer priority (keyword of the add*Control! functions, key priority in control.controllers, default 0). In each pass the controllers act by rank, smallest number first. A rank acts only if no controller with a smaller number moved its actuator in that pass: each of them is inside its deadband, at its limit, or parked. Controllers with the same number act together, so the default (all 0) is the loop without ranks. Unlike referencePriority of a machine, 0 is a rank here (the first), not "no preference".
A locked controller (the dead time of a sequential QSTS run) stays in its rank and is evaluated, but moves nothing. While it stands outside its band and not at its limit it holds the larger numbers; in its band or at its limit they act.
A controller is at its limit when its actuator stands at the end of its range:
| Controller | At its limit |
|---|---|
| Tap changer | ratio at the end of its control range: tap_min/tap_max of the controller where set, of the transformer otherwise (phase tap: phase_min_deg/phase_max_deg) |
Switched bank (step_mvar) | on its outermost block, or parked (no whole block brings the voltage closer to the target) |
| SVC | susceptance at bs_min_mvar/bs_max_mvar |
| Machine, STATCOM | reactive output at its Q limit (STATCOM: V * S_max, which moves with the terminal voltage) |
| TCSC, SSSC, UPFC, HVDC pair | at the end of their own range or rating |
The common case is a switched bank behind the tap changer of its bus:
control:
controllers:
bank_LV:
type: shunt_voltage
bus: LV
target_vm_pu: 1.0
bs_min_mvar: 0.0
bs_max_mvar: 20.0
step_mvar: 5.0
deadband_vm_pu: 0.02
priority: 1With the tap controller at rank 0 the bank switches only when the tap stands in its band or at a tap limit. At equal rank both move in the same pass, and the bank switches as soon as the bus leaves the bank's band, while the tap would have brought the voltage back alone. The cascade needs targets that agree within both deadbands (a bank at 1.01 pu behind a tap at 1.0 +/- 0.01 pu agrees): with targets further apart the lower rank pulls the voltage out of the tap's band whenever the tap is in band, and the two walk against each other at any ranks. The cross-type warning at registration names that case.
A tap controller can get its own control range inside the physical one (tap_min/tap_max on the power_transformer entry or as keywords of addPowerTransformerControl!). The range sets where the bank behind it takes over. A ratio outside the range goes onto its nearer end in the first pass, whatever the voltage error; until then the controller does not count as converged. The move logs a warning with the transformer, its start ratio and step, the limit and the ratio it goes to, once per controller and run; a QSTS run over its base case and all steps is one run. The entry below sets the range of the controller the case file puts on T1; on a transformer without a controller the entry adds one and needs target_bus and target_vm_pu as well:
control:
controllers:
tap_T1:
type: power_transformer
trafo: T1
mode: voltage
tap_min: 0.95
tap_max: 1.05A move along the limit does not hold the next rank: a controller that was at its limit at the end of the previous pass and is there again after its move (a STATCOM following V * S_max, a tap settling onto tap_min from a ratio a rounding error above it) lets the next rank act in the same pass. A last partial tap step onto a limit off the step grid is a move.
A waiting rank costs passes: after the last move of a higher rank one solve runs before the lower rank acts, so a long chain of ranks may need a larger control.max_outer_iterations. A controller held back proposes nothing and writes no trace row for that pass. control_priority(ctrl) returns the rank; a user-defined controller without a priority field ranks at 0.
Controllable elements (generic view)
Every registered controller describes itself in one vocabulary (record fields in the Use table above):
controllableElements(net) # -> Vector{NamedTuple}| Device | Actuator | Quantity |
|---|---|---|
| OLTC transformer | :tap_ratio | :bus_voltage |
| Phase-shifting transformer | :phase_shift_deg | :branch_active_power |
| Combined regulation | :tap_ratio_and_phase_shift | both |
| Machine remote voltage control | :machine_q_mvar | :bus_voltage |
| SVC (variable shunt) | :shunt_bs_mvar | :bus_voltage |
| MSC/MSR (switched shunt bank) | :shunt_bs_mvar | :bus_voltage |
| TCSC (series compensation) | :series_x_pu | :branch_active_power |
| Back-to-back HVDC pair | :hvdc_p_transfer_mw | :hvdc_transfer |
SVC: variable-shunt voltage control
addShuntVoltageControl!(net; bus, target_vm_pu, bs_min_mvar, bs_max_mvar, ...) adds an SVC controller: its own shunt element whose susceptance (MVAr at 1.0 p.u., capacitive positive) the outer loop moves by secant iteration to hold the bus voltage; at a limit the susceptance stays clamped (at_limit). step_mvar switches to the discrete MSC/MSR mode; the STATCOM alternative is addMachineVoltageControl! with s_max_mva. Limit physics of all three: FACTS Devices.
The bus must be PQ; a second shunt controller on the same bus is rejected, a tap controller regulating the same bus triggers the cross-type warning, except for a shunt controller at another priority with the same target within both deadbands (the cascade in Controller priority). runShortCircuit! and the power flow see the SVC only through its shunt stamp.
TCSC: series-reactance flow control
addSeriesReactanceControl!(net; fromBus, toBus, p_target_mw, x_min_pu, x_max_pu, ...) adds a TCSC controller on a line branch: the outer loop moves the series reactance x_pu within its range by secant iteration until the branch carries the active-power target (registered from-to direction), re-stamping the Y-bus before each solve; at a range end the branch is a fixed compensated line (at_limit). Transformer branches are rejected (taps own transformer reactance), and ranges whose series impedance magnitude enters the resonance guard eps_z are refused. Theory and the SSSC mode (v_inj_max_pu): Series Compensation (TCSC); the UPFC (addUpfcControl!): FACTS Devices.
Master/slave groups for parallel transformers
Two transformers in parallel between the same busbars regulate as a group; unequal tap positions would drive a circulating reactive power around the loop, and two secant loops on one target voltage oscillate against each other:
addPowerTransformerControl!(net; trafo = "1", followers = ["2"],
mode = :voltage, target_bus = "LV",
target_vm_pu = 1.0, deadband_vm_pu = 5e-3)The master runs the normal discrete voltage loop; every accepted master move is mirrored onto the followers step-synchronously (whole steps of each follower's own tap_step, clamped to its range). Declaratively the group is the followers list on a power_transformer entry. A second independent voltage controller on an already-regulated target bus triggers a warning; a follower cannot carry its own ratio controller and cannot follow two groups. Synchronized steps multiply the voltage effect per master step by the group size, so the deadband must cover at least half the aggregated step effect.
CGMES: RatioTapChangers sharing one RegulatingControl (TapChanger.TapChangerControl) import as a group, the first enabled one as master (message follows the group of ...); controlEnabled = false stays fixed. The exporter writes one shared TapChangerControl per active voltage tap controller (mode voltage, regulated-bus terminal in EQ; enabled, targetValue/targetDeadband in kV in SSH), referenced by the master's and every follower's RatioTapChanger with controlEnabled = true, so a group survives a CGMES roundtrip.
Transformer regulation theory: OLTC, PST, and combined regulation
A regulated transformer inserts an additional voltage into the winding; its phase relative to the winding voltage distinguishes three cases:
- In-phase regulation, OLTC (German Längsregelung): the added voltage is parallel to the winding voltage, so only the magnitude of the complex turns ratio changes: the ordinary ratio tap, acting mainly on voltage magnitudes and reactive-power flow.
- Quadrature regulation, PST (German Querregelung): the added voltage is perpendicular (90°), so mostly the angle changes: the phase-shifting transformer or quadrature booster, acting mainly on active-power flow.
- Combined (oblique) regulation (German Schrägregelung): the added voltage has an intermediate angle, or, as modeled here, the unit carries both an in-phase and a quadrature tap:
n = ρ · e^{jα}with independently switchable magnitudeρ(ratio tap) and angleα(phase tap).
In the branch model these are the independent fields tap_ratio (with tap_min/max/step) and phase_shift_deg (phase_min/max/step_deg); both enter the complex ratio of the transformer branch. On a transformer without a typed tap model a ratio step does not move the angle and a phase step does not move the magnitude; a typed PhaseTapChangerModel on the winding couples them like a real asymmetrical regulator, and the branch model derives the split of its move.
Control: why V→ratio and P→phase may be split
In transmission grids voltage magnitudes respond mainly to the ratio tap (V-Q coupling) and active-power flow to the phase angle (P-θ coupling), so combined-regulation units usually run a voltage regulator on the in-phase stage and an active-power regulator on the quadrature stage (the "angle controller" regulates a power setpoint). Sparlectra supports both:
One combined controller:
mode = :voltage_and_branch_active_powerwithcontrol_ratio = trueandcontrol_phase = true(one status, one report row;examples/others/tap_control_demo_grid.jl).Two independent controllers on one transformer (split combined regulation): a
mode = :voltagecontroller owning the ratio tap and amode = :branch_active_powercontroller owning the phase tap:addTapController!(net; trafo = "T_SCHRAEG", mode = :voltage, target_bus = "Load_MV", target_vm_pu = 1.02, control_ratio = true, control_phase = false, deadband_vm_pu = 5e-3) addTapController!(net; trafo = "T_SCHRAEG", mode = :branch_active_power, target_branch = ("HV", "MV"), p_target_mw = 120.0, control_ratio = false, control_phase = true, deadband_p_mw = 2.0)Each channel keeps its own target, deadband, status, and report/trace rows. Demo:
examples/others/tap_control_schraeg_two_controllers.jl.
Per-actuator exclusivity and step sizing
Each actuator (ratio tap, phase tap) is driven by at most one active controller: two controllers on one transformer need disjoint actuator sets, and a second claim on a driven actuator raises an error. With discrete taps the deadband must cover at least the effect of half a tap step on the controlled quantity (one 0.5° phase step moving about 2.5 MW requires deadband_p_mw ≥ ~1.5); a tighter deadband makes the controller hunt around the target until max_outer_iterations stops the loop.
On a transformer whose winding carries a typed tap model (taps, phase_taps, see Branch model), the controller moves the model's step and the resolver rewrites ratio, shift and the tap dependent reactance; the step sizes above then are the model's own, which for a symmetrical or asymmetrical phase shifter are not uniform in degrees. The controller report rows show the model step as the position.