Transformer taps: moving voltage, moving power

Level: Advanced, companion of basic-tour chapter 4.

Open in Colab

Note: This workshop was created with AI assistance and is reviewed and curated by the maintainer; it is not a fully machine-generated text.

A transformer enters the power flow with exactly two adjustable numbers: the winding ratio $\tau$ and the phase shift $\varphi$. The ratio tap (OLTC) moves $\tau$ and thereby VOLTAGE; the phase tap (PST, in German a Schrägregler) moves $\varphi$ and thereby ACTIVE POWER. In this notebook you compute real tap positions with the device formulas of Sparlectra.jl, watch each tap type move its quantity, close the loop with the outer phase-tap controller, and finish with a three-winding transformer carrying a tap on one leg.

Note: On Google Colab the install cell takes a few minutes on a fresh session (package download and precompilation). Colab's Julia version may change over time; this notebook targets Julia ≥ 1.12.

Warm-up and shared helpers

Julia compiles each function on first use. This cell loads the package, defines the helpers all chapters share, and warms the two paths the notebook exercises (plain power flow and the outer control loop), so the chapters below run at full speed.

using Sparlectra

# solve helper: converged power flow or an error
function solve!(net)
  ite, erg = runpf!(net, 50, 1e-9, 0)
  erg == 0 || error("Power flow did not converge (status = $erg)")
  calcNetLosses!(net)
  return ite
end

bus_vm(net, bus) = round(get_bus_vm_pu(net, bus); digits = 4)

# warm both paths on a throwaway 2-bus net with a transformer
wnet = Net(name = "warmup", baseMVA = 100.0)
addBus!(net = wnet, busName = "A", vn_kV = 110.0)
addBus!(net = wnet, busName = "B", vn_kV = 20.0)
addProsumer!(net = wnet, busName = "A", type = "EXTERNALNETWORKINJECTION", referencePri = "A", vm_pu = 1.0, va_deg = 0.0)
addProsumer!(net = wnet, busName = "B", type = "ENERGYCONSUMER", p = 10.0, q = 3.0)
addPIModelTrafo!(net = wnet, fromBus = "A", toBus = "B", r_pu = 0.01, x_pu = 0.08, b_pu = 0.0, ratio = 1.0, shift_deg = 0.0, status = 1)
t_pf = @elapsed solve!(wnet)
addPowerTransformerControl!(wnet; trafo = "1", mode = :branch_active_power, target_branch = ("A", "B"), p_target_mw = 10.0, control_ratio = false, control_phase = true, deadband_p_mw = 5.0)
wnet.branchVec[1].has_phase_tap = true
wnet.branchVec[1].phase_min_deg = -10.0
wnet.branchVec[1].phase_max_deg = 10.0
wnet.branchVec[1].phase_step_deg = 0.5
t_ctrl = @elapsed run_sparlectra(net = wnet)
println("warm: power flow ", round(t_pf; digits = 2), " s, control loop ", round(t_ctrl; digits = 2), " s (first calls compile)")
warm: power flow 0.02 s, control loop 0.49 s (first calls compile)

Two taps, two jobs

Every transformer branch is stamped into the Y-bus as (see the Branch Model page):

\[Y_{br} = \begin{bmatrix} \frac{1}{\tau^2}\left(y_{ser} + \frac{y_{shunt}}{2}\right) & -y_{ser}\,\frac{1}{\tau e^{-j\varphi}} \\ -y_{ser}\,\frac{1}{\tau e^{j\varphi}} & y_{ser} + \frac{y_{shunt}}{2} \end{bmatrix}\]

\[\tau\]

scales voltage magnitude across the transformer, so the RATIO tap is the voltage lever. $\varphi$ shifts the voltage ANGLE, and since $P \sim \sin(\delta_1 - \delta_2)$, the PHASE tap is the active-power lever. Sparlectra ships the device math for both: PowerTransformerTaps with calcRatioTapCorrection for the OLTC, and PhaseTapChangerModel with calcPhaseTapAngleRatio for the PST.

Chapter 1: the ratio tap (OLTC) moves voltage

Example 1: the ratio tap moves voltage. A 380/110 kV transformer feeds a 60 MW load. The OLTC has 19 positions (-9 to +9) of 3.8 kV each, exactly 1 percent of 380 kV per step. We compute $\tau$ for a few positions with the device formula and watch the load-side voltage follow:

  S (slack, 380 kV) --- line --- A ==OLTC== B (110 kV, load 60 MW)
function feeder(ratio)
  net = Net(name = "oltc_feeder", baseMVA = 100.0)
  addBus!(net = net, busName = "S", vn_kV = 380.0)
  addBus!(net = net, busName = "A", vn_kV = 380.0)
  addBus!(net = net, busName = "B", vn_kV = 110.0)
  addProsumer!(net = net, busName = "S", type = "EXTERNALNETWORKINJECTION", referencePri = "S", vm_pu = 1.0, va_deg = 0.0)
  addProsumer!(net = net, busName = "B", type = "ENERGYCONSUMER", p = 60.0, q = 20.0)
  addPIModelACLine!(net = net, fromBus = "S", toBus = "A", r_pu = 0.01, x_pu = 0.06, b_pu = 0.0, status = 1)
  addPIModelTrafo!(net = net, fromBus = "A", toBus = "B", r_pu = 0.01, x_pu = 0.10, b_pu = 0.0, ratio = ratio, shift_deg = 0.0, status = 1)
  validate!(net = net)
  solve!(net)
  return net
end

for step in (-5, 0, 5)
  taps = PowerTransformerTaps(Vn_kV = 380.0, step = step, lowStep = -9, highStep = 9, neutralStep = 0, voltageIncrement_kV = 3.8)
  tau = calcRatioTapCorrection(taps)
  net = feeder(tau)
  println("step ", lpad(step, 3), ": tau = ", round(tau; digits = 4), "  ->  Vm(B) = ", bus_vm(net, "B"), " pu")
end
step  -5: tau = 0.95  ->  Vm(B) = 1.0025 pu
step   0: tau = 1.0  ->  Vm(B) = 0.9489 pu
step   5: tau = 1.05  ->  Vm(B) = 0.9002 pu

Reading aid (Example 1): five steps move tau by 5 percent and the load voltage by roughly the same amount, in the opposite direction: raising tau means more turns on the primary, so the secondary voltage drops. This manual sweep is exactly what the OLTC CONTROLLER automates against a voltage target; the closed loop is chapter 4 of the workshop tour.

Chapter 2: the phase tap (PST) moves power

Example 2: the phase tap moves power. Now the loop network every PST lives for: a transformer in parallel with a line. Without a phase shift the flow splits by impedance and stays put. Every phase-tap step tilts the angle across the transformer and REROUTES active power between the two parallel paths:

       +=== PST (tau, phi) ===+
  S ---|                      |--- M --- line --- L (load 70 MW)
       +------- line ---------+

The asymmetrical PST (the classical Schrägregler) injects its boost voltage at a winding angle, here 60 degrees; each step therefore changes BOTH the angle and, slightly, the ratio. calcPhaseTapAngleRatio returns the effective pair for a given step:

function pst_loop(ratio, shift_deg)
  net = Net(name = "pst_loop", baseMVA = 100.0)
  for b in ("S", "M", "L")
    addBus!(net = net, busName = b, vn_kV = 110.0)
  end
  addProsumer!(net = net, busName = "S", type = "EXTERNALNETWORKINJECTION", referencePri = "S", vm_pu = 1.0, va_deg = 0.0)
  addProsumer!(net = net, busName = "L", type = "ENERGYCONSUMER", p = 70.0, q = 20.0)
  addPIModelTrafo!(net = net, fromBus = "S", toBus = "M", r_pu = 0.01, x_pu = 0.08, b_pu = 0.0, ratio = ratio, shift_deg = shift_deg, status = 1)
  addPIModelACLine!(net = net, fromBus = "S", toBus = "M", r_pu = 0.03, x_pu = 0.20, b_pu = 0.0, status = 1)
  addPIModelACLine!(net = net, fromBus = "M", toBus = "L", r_pu = 0.02, x_pu = 0.12, b_pu = 0.0, status = 1)
  validate!(net = net)
  solve!(net)
  return net
end

pst = step -> PhaseTapChangerModel(kind = :asymmetrical, step = step, lowStep = -8, highStep = 8, neutralStep = 0, voltage_step_increment = 0.0125, winding_connection_angle_deg = 60.0)
for step in (-6, 0, 6)
  tap = calcPhaseTapAngleRatio(pst(step))
  net = pst_loop(tap.effective_ratio, tap.effective_shift_deg)
  println("step ", lpad(step, 3), ": phi = ", lpad(round(tap.effective_shift_deg; digits = 2), 6), " deg, tau = ", round(tap.effective_ratio; digits = 4), "  ->  P(trafo) = ", round(get_branch_p_from_to_mw(net, "S", "M"); digits = 1), " MW of 70")
end
step  -6: phi =   3.86 deg, tau = 1.0366  ->  P(trafo) = 26.8 MW of 70
step   0: phi =   -0.0 deg, tau = 1.0  ->  P(trafo) = 51.1 MW of 70
step   6: phi =  -3.58 deg, tau = 0.962  ->  P(trafo) = 76.1 MW of 70

Reading aid (Example 2): at neutral the transformer takes the larger share (it has the lower reactance). Six steps of phase shift swing tens of MW from one parallel path to the other while the total delivery stays 70 MW plus losses: the PST does not produce power, it REROUTES it. The :symmetrical kind does the same with tau pinned to exactly 1.0 (pure angle, no voltage side effect), which is the in-line quadrature booster.

Chapter 3: closing the loop, and the X(alpha) subtlety

Example 3: closing the loop. In operation nobody dials raw steps: a target flow is given and the outer control loop moves the tap, here on the same S/M/L parallel-path loop as Example 2 (diagram there), with the source raised to 1.02 pu. addPowerTransformerControl! with control_phase = true regulates the active power through the transformer. One physical subtlety makes the difference to Example 2: a real PST's series reactance is not constant, it follows the device characteristic $X(\alpha)$ as the boost winding moves. Attach a PhaseTapChangerModel with x_min/x_max to the winding and every accepted tap move re-stamps the branch with the reactance at the new angle:

net = Net(name = "pst_ctrl", baseMVA = 100.0)
for b in ("S", "M", "L")
  addBus!(net = net, busName = b, vn_kV = 110.0)
end
addProsumer!(net = net, busName = "S", type = "EXTERNALNETWORKINJECTION", referencePri = "S", vm_pu = 1.02, va_deg = 0.0)
addProsumer!(net = net, busName = "L", type = "ENERGYCONSUMER", p = 70.0, q = 20.0)
addPIModelTrafo!(net = net, fromBus = "S", toBus = "M", r_pu = 0.01, x_pu = 0.08, b_pu = 0.0, ratio = 1.0, shift_deg = 0.0, status = 1)
addPIModelACLine!(net = net, fromBus = "S", toBus = "M", r_pu = 0.03, x_pu = 0.20, b_pu = 0.0, status = 1)
addPIModelACLine!(net = net, fromBus = "M", toBus = "L", r_pu = 0.02, x_pu = 0.12, b_pu = 0.01, status = 1)
tbr = getNetBranch(net = net, fromBus = "S", toBus = "M")
tbr.has_phase_tap = true
tbr.phase_min_deg = -10.0
tbr.phase_max_deg = 10.0
tbr.phase_step_deg = 0.5
# the device characteristic: X grows from x_min at neutral to x_max at
# the range end
net.trafos[1].side1.phase_taps = Sparlectra.PhaseTapChangerModel(kind = :symmetrical, step = 0, lowStep = -10, highStep = 10, neutralStep = 0, voltage_step_increment = 0.01, x_min = 0.08, x_max = 0.16)

run_sparlectra(net = net)
p0 = get_branch_p_from_to_mw(net, "S", "M")
addPowerTransformerControl!(net; trafo = string(tbr.branchIdx), mode = :branch_active_power, target_branch = ("S", "M"), p_target_mw = p0 - 8.0, control_ratio = false, control_phase = true, deadband_p_mw = 4.0)
run_sparlectra(net = net)
println("controller: P(trafo) ", round(p0; digits = 1), " -> ", round(get_branch_p_from_to_mw(net, "S", "M"); digits = 1), " MW (target ", round(p0 - 8.0; digits = 1), ")")
println("            settled at phi = ", tbr.phase_shift_deg, " deg with x_pu = ", round(tbr.x_pu; digits = 4), " (device characteristic, not the 0.08 import value)")
controller: P(trafo) 51.0 -> 44.4 MW (target 43.0)
            settled at phi = 1.0 deg with x_pu = 0.0824 (device characteristic, not the 0.08 import value)

Reading aid (Example 3): the converged reactance sits ABOVE the import-time 0.08 pu because the controller left neutral and the branch follows $X(\alpha)$. Without the typed model the loop would steer the same target with a slightly wrong (static) reactance; the runnable comparison of both variants is exp_pst_reactance_coupling.jl in the repository.

Chapter 4: the three-winding transformer

Example 4: the three-winding transformer. A 3WT is solved as its STAR EQUIVALENT: one auxiliary bus in the middle and three two-winding legs, one per winding. A tap changer always sits on ONE winding, so in the equivalent it lands on one leg. The test network hangs the star between a slack feeder and an MV load:

  B1 (slack) ---- B2 (380 kV, HV) ==leg 1==+
                                           |
  B5 (load) ----- B3 (110 kV, MV) ==leg 2==+ AUX (star point)
                                           |
                  B4 ( 20 kV, LV) ==leg 3==+

  ----  AC line    ==leg==  2WT leg of the star equivalent
  B5 carries the 80 MW load, B4 a 5 MVAr shunt
function build_3wt(; oltc_step::Int)
  net = Net(name = "3wt_demo", baseMVA = 1000.0)
  addBus!(net = net, busName = "B1", vn_kV = 380.0)
  addBus!(net = net, busName = "B2", vn_kV = 380.0)
  addBus!(net = net, busName = "B3", vn_kV = 110.0)
  addBus!(net = net, busName = "B4", vn_kV = 20.0)
  addBus!(net = net, busName = "B5", vn_kV = 110.0)
  addProsumer!(net = net, busName = "B1", type = "EXTERNALNETWORKINJECTION", vm_pu = 1.0, va_deg = 0.0, referencePri = "B1")
  addACLine!(net = net, fromBus = "B1", toBus = "B2", length = 1.0, r = 0.01, x = 0.10)
  # the star equivalent by hand: AUX bus plus three 2WT legs; the OLTC
  # ratio (device formula) is applied to the HV leg only
  taps = PowerTransformerTaps(Vn_kV = 380.0, step = oltc_step, lowStep = -9, highStep = 9, neutralStep = 0, voltageIncrement_kV = 3.8)
  addBus!(net = net, busName = "AUX", vn_kV = 380.0, isAux = true)
  add2WTPIModelTrafo!(net = net, fromBus = "AUX", toBus = "B2", side = 1, r = 0.20, x = 4.00, b = 0.0, status = 1, ratedU = 380.0, ratedS = 1000.0, ratio = calcRatioTapCorrection(taps), shift_deg = 0.0)
  add2WTPIModelTrafo!(net = net, fromBus = "AUX", toBus = "B3", side = 1, r = 0.30, x = 6.00, b = 0.0, status = 1, ratedU = 380.0, ratedS = 500.0, ratio = 1.0, shift_deg = 0.0)
  add2WTPIModelTrafo!(net = net, fromBus = "AUX", toBus = "B4", side = 1, r = 0.40, x = 10.00, b = 0.0, status = 1, ratedU = 380.0, ratedS = 200.0, ratio = 1.0, shift_deg = 0.0)
  addACLine!(net = net, fromBus = "B3", toBus = "B5", length = 1.0, r = 0.01, x = 0.10)
  addProsumer!(net = net, busName = "B5", type = "ENERGYCONSUMER", p = 80.0, q = 30.0)
  addShunt!(net = net, busName = "B4", pShunt = 0.0, qShunt = 5.0)
  validate!(net = net)
  solve!(net)
  return net
end

for step in (0, 5)
  net3wt = build_3wt(oltc_step = step)
  println("OLTC step ", step, " on the HV leg: Vm(B3) = ", bus_vm(net3wt, "B3"), " pu, Vm(B4) = ", bus_vm(net3wt, "B4"), " pu")
end
OLTC step 0 on the HV leg: Vm(B3) = 0.9942 pu, Vm(B4) = 0.996 pu
OLTC step 5 on the HV leg: Vm(B3) = 1.0442 pu, Vm(B4) = 1.0459 pu

Reading aid (Example 4): the tap sits on the HV leg, so BOTH output windings move together; a tap on the MV leg would move only B3. One honest note: the tap objects that create3WTWindings! can carry are not yet wired into the Net-building 3WT path, so this notebook computes the correction with the device formula and applies it to the leg explicitly, which is the same arithmetic the wiring would do. The full three-case study (OLTC, PST asymmetrical, PST symmetrical on a 3WT) is exp_3wt_phase_taps.jl in the repository.