Network Branch and Transformer Model
Branches, transformers and phase-shifting transformers (PSTs) share one four-terminal equivalent circuit. Typed tap-changer models feed it, an outer-loop control regulates taps, and the models map onto the ENTSO-E CGMES data model.
1. Common branch model
Each branch uses the same four-terminal model with a complex transformation ratio $N$ on the from side: $N = 1$ for power lines, a complex value for transformers. The branch admittance matrix $Y_{br}$ is:
\[Y_{br} = \begin{bmatrix} \frac{1}{\tau^2} \left( y_{ser} + y_{0,from} \right) & -y_{ser} \frac{1}{\tau e^{-j\phi}} \\ -y_{ser} \frac{1}{\tau e^{j\phi}} & y_{ser} + y_{0,to} \end{bmatrix}\]
with y_ser the series admittance from the resistance R and the reactance X, and $y_{0,from}$, $y_{0,to}$ the shunt arms at the two terminals (conductance G, susceptance B):
\[N = \tau e^{j\phi}\]
\[y_{ser} = \frac{1}{R + jX}\]
\[y_{0,from} = G_{from} + jB_{from}, \qquad y_{0,to} = G_{to} + jB_{to}, \qquad y_{shunt} = y_{0,from} + y_{0,to} = G + jB\]
The branch stores the two arms (g_from_pu, b_from_pu, g_to_pu, b_to_pu) and the totals g_pu, b_pu as their sums. MATPOWER and the symmetric pi are the case $y_{0,from} = y_{0,to} = (G + jB)/2$, which every builder produces when given totals only; the from arm sits behind the ideal transformer, so a transformer whose magnetizing admittance belongs to one side keeps it there (see Where the magnetizing admittance sits).
The magnitude $\tau$ is the off-nominal tap ratio, the angle $\phi$ the phase shift. A pure ratio tap changer moves $\tau$, a pure phase shifter $\phi$, a combined regulator (German Schrägregler) both.
Circuit diagram
y_ser
x--┓┏---------###----------x
|| | |
|| # y_0,from # y_0,to
|| | |
x--┛┗----------------------x
N = tau * exp(j * phi)Sign and conjugation convention
With series admittance $y$, the shunt arms $y_{0,from}$ and $y_{0,to}$, and from-side tap $t = \tau e^{j\phi}$, the stamped entries (calcAdmittance) are:
\[\begin{aligned} Y_{ff} &= \frac{y + y_{0,from}}{\lvert t \rvert^2} \\ Y_{ft} &= -\frac{y}{\overline{t}} \\ Y_{tf} &= -\frac{y}{t} \\ Y_{tt} &= y + y_{0,to} \end{aligned}\]
With the symmetric split both arms are $0.5\,y_{sh}$ and the entries are the classic MATPOWER stamp.
The tap is applied on the from side. Reversing a PST with $\tau = 1$ is electrically a sign flip of $\phi$; with an off-nominal ratio, reversing the orientation also moves the ratio tap and is not a pure sign change.
2. Y-bus assembly
Diagonal entries (π-model + shunts)
The diagonal Y-bus entry of node $i$ is the nodal self-admittance: the sum of what every branch at the bus stamps on its terminal, plus the explicit bus shunt:
\[Y_{ii} = \sum_{k \in \mathcal{N}(i)} \left( y_{ik} + y_{0,i}^{(ik)} \right) + y_i^{sh}\]
with $y_{ik}$ the series admittance of branch $i-k$, $y_{0,i}^{(ik)}$ its shunt arm at the terminal $i$ ($y_{ik}^{sh}/2$ for the symmetric split) and $y_i^{sh}$ the explicit shunt admittance at bus $i$. The line is the case $t = 1$ of the stamp in section 1; a transformer divides the stamp of its from terminal by $\lvert t \rvert^2$ ($Y_{ff}$ above). The off-diagonal entry of a line is
\[Y_{ik} = -y_{ik}\]
(a transformer: $-y_{ik}/\overline{t}$ and $-y_{ik}/t$, see $Y_{ft}$ and $Y_{tf}$). For a network of lines the diagonal is therefore the negative off-diagonal row sum plus the shunt arms and the bus shunt:
\[Y_{ii} = -\sum_{k \neq i} Y_{ik} + \sum_{k \in \mathcal{N}(i)} y_{0,i}^{(ik)} + y_i^{sh}\]
Only without any shunt (no line charging, no bus shunt) does the row sum vanish, $Y_{ii} = -\sum_{k \neq i} Y_{ik}$.
The branch builders (addACLine!, addACLinePerKm!, addPIModelACLine!, addPIModelTrafo!) stamp series admittance plus half shunt on each side unless the four terminal values g_from_pu, b_from_pu, g_to_pu, b_to_pu are given (all four or none); explicit shunts are added as nodal shunt terms when bus_shunt_model = "admittance".
Where the magnetizing admittance sits
A transformer's magnetizing branch ($G$, $B$ of the no-load test) is a one-sided quantity. PowSyBl and OpenLoadFlow put it wholly on side 1, behind the ideal transformer (twtSplitShuntAdmittance = false), and the PowSyBl importer keeps it there as the from arm with the to arm zero. A CGMES PowerTransformerEnd carries g, b per end; the importer refers both ends to the to-side base, sums them and puts half of the total on each terminal (since 0.41.0), the from half behind the tap. The SV of the ENTSO-E test configurations is computed this way: on SmallGrid and MicroGrid BE and NL the units at the transformer ends match it exactly, with the per-end placement they missed it by up to 3.6 MVAr. A three-winding leg puts the admittance of its end at the star point (since 0.42.0), the arm at the leg's bus is zero: a leg without a tap changer runs from the star point to its bus and carries it as the from arm behind the ratio, a leg with a tap changer runs from its bus to the star point and carries it as the to arm on the star base. With the admittance at the star the 3W terminal flows match the SV of the ENTSO-E sets; on MicroGrid BE the largest voltage deviation after the power flow drops from 1.13e-4 to 8.1e-5 pu. MATPOWER has no place for the split: its reader produces the symmetric half, its writer puts the symmetric part on the branch and the excess on a bus shunt named after the branch (see MATPOWER).
Bus-shunt modeling modes
Bus shunts from sources such as the MATPOWER Gs/Bs columns enter in one of two ways:
"admittance"(default): the bus shunt admittance $y_i^{sh} = G_i + jB_i$ is stamped into the Y-bus diagonal as part of $Y_{ii}$."voltage_dependent_injection": the shunt is not stamped into Y-bus; its power is evaluated in the nonlinear injection/mismatch path as a local voltage-dependent term.
For a bus shunt admittance $y_i^{sh}$ and local voltage magnitude $|V_i|$:
\[S_i^{sh} = |V_i|^2 \overline{y_i^{sh}}\]
A positive conductance contributes positive active power; the reactive sign follows the conjugate of the shunt admittance. The rectangular mismatch uses S_calc - S_spec, so the injection mode subtracts $S_i^{sh}$ from the specified net injection. Both modes give the same solution and never double-count: each shunt is either stamped into Y-bus or an injection term.
3. One-sided open branches
A branch carries two terminal flags from_status/to_status next to the aggregate status. The aggregate stays the user-facing switch (setBranchStatus! sets all three; status = 1 iff both terminals are closed); setBranchTerminalStatus!(br; from =, to =) opens or closes single terminals. The terminal state is one of :closed, :open_from, :open_to, :open.
The pi reduction
Take the pi model with series admittance $Y_s = 1/(r + jx)$ and the shunt arms $Y_{0,from}$ at the closed and $Y_{0,to}$ at the open terminal (both $(g + jb)/2$ for the symmetric split), terminal to open, from closed, no load at the open end. Seen from the closed bus the branch collapses exactly to the input admittance
\[Y_{in} = Y_{0,from} + \frac{Y_s Y_{0,to}}{Y_s + Y_{0,to}}\]
Because $|Y_s| \gg |Y_{0,to}|$ for any realistic line, $Y_{in} \approx Y_{0,from} + Y_{0,to} = g + jb$: the one-sided open line draws its full charging, not half of it, and a transformer whose magnetizing arm sits on the closed side draws exactly that arm.
The implementation uses the equivalent Schur-complement form on the two-port from calcAdmittance, which already carries the complex ratio: with the to end open $Y_{in} = Y_{11} - Y_{12} Y_{21} / Y_{22}$, with the from end open $Y_{in} = Y_{22} - Y_{21} Y_{12} / Y_{11}$. Lines and transformers (off-nominal ratio, phase shift) are covered uniformly.
Open-end voltage and power
The voltage at the open terminal follows from the divider (zero current at the open end): with to open $U_{open} = -Y_{21}/Y_{22} \cdot U_{from}$. It reproduces the Ferranti rise ($|U_{open}| > |U_{from}|$ for $b > 0$) and is reported as a branch result (open_end_vm_pu / open_end_va_deg) without adding a node to the solved system; the open bus itself is isolated unless other branches feed it.
The closed terminal carries $S = |U|^2 \cdot \overline{Y_{in}}$: the imaginary part is the charging reactive power, the real part the power absorbed by $g$ plus the ohmic loss of the charging current in $r$, small but not zero. The open terminal carries $S = 0$, and the branch loss equals the closed-terminal power.
The equivalent dangling-node formulation
Keeping the full branch and attaching an auxiliary zero-injection PQ bus at the open end is exactly equivalent for a pure pi branch (the test suite uses it as the correctness anchor), but it adds one bus per open terminal and would change bus counts, island reports, result tables and the CGMES roundtrip identity. Equipment at the open end (a shunt, a load) would need it and is out of scope.
In the solvers the Y-bus stamps only $Y_{in}$ on the diagonal of the closed bus, the DC power flow ignores the branch ($B'$ carries no shunts), and the short-circuit matrix drops it like the charging arms of closed branches. Results mark partial rows open@to/open@from, count them under Open terminals in the header, and carry terminal_state plus the open-end voltage in ACPFlowReport.branches and the detailed CSV. In the bus table an isolated open-end bus shows the Ferranti voltage in its V/phi columns, flagged open-end in the Control column (skipped when several one-sided-open branches end at the bus; an energized bus keeps its solved voltage). Example: exp_open_terminal_line.jl; the basic workshop tour shows it in chapter 2.
4. Tap-changer modelling layers
Source-format parsing, tap-changer semantics, equivalent-circuit calculation and the solver representation are separate layers:
Importer (MatpowerIO, DTFImporter, ...)
| maps source fields -> tap-changer model structs, no physics formulas
v
transformer.jl data types only (no behaviour)
v
equicircuit.jl pure functions: model + tap position -> (ratio, shift_deg, x_pu?)
v
Branch.ratio / Branch.shift_deg / Branch.x_pu
v
Y-bus stamping / rectangular NR / outer-loop controlEvery tap/PST formula lives once, in equicircuit.jl. Importers only construct model structs and call the helpers.
Data types (transformer.jl)
All tap-changer models share the supertype AbstractTapChangerModel.
Ratio tap changer: PowerTransformerTaps carries the tap range and step definition (step, lowStep, highStep, neutralStep, voltageIncrement_kV / tapStepPercent, tapSign) plus nameplate metadata (neutralU, neutralU_ratio). Its convention field makes the ratio convention explicit; :neutral_relative applies the correction corr = 1 + (step - neutralStep)·tapStepPercent/100 as a divisor on the winding ratio. Side information lives on PowerTransformer.tapSideNumber.
Phase tap changer: PhaseTapChangerModel classifies the PST technology via a kind field:
kind::Symbol :symmetrical | :asymmetrical | :tabular
(quadrature booster = :asymmetrical with ψ = 90°, no own kind)
step, lowStep, highStep, neutralStep
voltage_step_increment # per-step voltage increment (linear/nonlinear)
step_phase_shift_increment # per-step phase increment (linear models)
winding_connection_angle_deg # ψ, only for :asymmetrical
x_min, x_max # X(0), X(αmax) for tap-dependent reactance
table::Union{Nothing,Vector{TapTablePoint}} # used when kind == :tabular
convention::SymbolTap table: a PhaseTapChangerModel(kind = :tabular) is backed by a non-empty vector of TapTablePoint rows (step, ratio, angle_deg, optional x_pu) with strictly ascending, unique steps (validated, never silently sorted). lowStep/highStep default to the table range, neutralStep must be a step of the table, and the formula parameters (voltage_step_increment, winding_connection_angle_deg, x_min, x_max) must be nothing. A table overrides the formula path whenever present.
Both kinds attach to a winding: PowerTransformerWinding has a taps::Union{Nothing,PowerTransformerTaps} slot and a parallel phase_taps::Union{Nothing,PhaseTapChangerModel} slot, as in CGMES, where a tap changer hangs on a transformer end.
winding_connection_angle_deg (ψ) is not a symmetrical-components or sequence angle; Sparlectra works in the positive sequence, and ψ lives there. ψ is the angle at which a regulator's additional voltage is injected relative to the base voltage, the geometry of the regulating vector in the complex voltage plane:
\[\text{regulating vector} = 1 + f \cdot e^{j\psi}, \qquad f = (\text{step} - \text{neutralStep}) \cdot u\]
ψ decides how a tap move splits between magnitude and phase: at ψ = 0° the added voltage is in phase (a pure longitudinal regulator, the regulating vector stays real, shift_deg is exactly 0), at ψ = 90° in quadrature (a quadrature booster, mainly a phase shift), and for 0° < ψ < 90° ratio and phase change in the proportion set by ψ (a combined regulator, Schrägregler).
From ψ and the tap fraction f, calcPhaseTapAngleRatio derives the effective ratio and shift_deg stamped into the branch (from-side convention: ratio = 1/|v|, shift = -arg(v)).
Constructing transformers
Ratio (OLTC) tap changer on a winding:
taps = PowerTransformerTaps(
Vn_kV = 110.0,
step = 0, lowStep = -9, highStep = 9, neutralStep = 0,
voltageIncrement_kV = 1.1, # per-step voltage increment
)
# convention defaults to :neutral_relativeSymmetrical phase shifter (pure angle regulation):
pst_sym = PhaseTapChangerModel(
kind = :symmetrical,
step = 3, lowStep = -10, highStep = 10, neutralStep = 0,
voltage_step_increment = 0.012, # per-step, pu of rated voltage
)Asymmetrical phase shifter / combined regulator (ψ ≠ 0):
pst_skew = PhaseTapChangerModel(
kind = :asymmetrical,
step = 7, lowStep = -13, highStep = 13, neutralStep = 0,
voltage_step_increment = 0.18 / 13, # e.g. 18 % over 13 steps
winding_connection_angle_deg = 60.0,
)
# quadrature booster is the same with winding_connection_angle_deg = 90.0Tabular phase shifter (table overrides formulas; carries no formula parameters):
table = [
TapTablePoint(step = -1, ratio = 1.00, angle_deg = -3.0, x_pu = 0.045),
TapTablePoint(step = 0, ratio = 1.00, angle_deg = 0.0, x_pu = 0.040),
TapTablePoint(step = 1, ratio = 1.00, angle_deg = 3.0, x_pu = 0.045),
]
pst_tab = PhaseTapChangerModel(
kind = :tabular,
neutralStep = 0, # must exist in the table
table = table, # lowStep/highStep derived from the table
)Attaching a phase-tap model when building a transformer branch:
addPIModelTrafo!(
net = net,
fromBus = "B1", toBus = "B2",
r_pu = 0.01, x_pu = 0.08, b_pu = 0.0,
ratio = 1.0, shift_deg = 0.0, status = 1,
phase_taps = pst_skew, # the model drives the branch from here on
)The resolver
A winding that carries a typed model (taps, phase_taps) drives its branch. resolve_branch_taps! (equicircuit.jl) runs when the transformer branch is built and whenever a tap controller moves a step: it takes ratio and shift_deg of the winding as the neutral point, multiplies the ratio-tap correction and the phase model's effective ratio onto it, adds the phase model's shift, derives the branch's tap grid (tap_min, tap_max, tap_step, phase_min_deg, phase_max_deg, mean degree per step) from the model ranges, applies the tap-changer model the transformer was built with (the tap_changer_model keyword of addPIModelTrafo!, kept as Branch.tap_correction; DTF passes model.tap_changer_model, SCF the entry of the transformer) to r_pu/x_pu from the equipment base, for an asymmetrical phase model only, and takes the model's own X(alpha) when it carries x_min/x_max or a table. The branch is then taps_derived.
With a model present the branch always shows the model's values; when the values the branch was built with differ by more than 1e-9, one line per transformer in net.tapModelNotices says what was replaced and at which step, and a service run (Web UI, run_powerflow_api) writes those lines to the artifact tap_models.log. Without a model the explicit ratio/shift_deg and the legacy degree grid stay as they were. Controllers move the step of a modelled transformer, never ratio/shift directly (probe and update pick the step closest to the proposal); the tap estimation of the state estimator takes the model steps as its states and fixes them on the model's own steps.
Behaviour (equicircuit.jl)
The equivalent-circuit helpers turn a model plus a tap position into the branch quantities, one pure function per formula family:
| Function | Purpose |
|---|---|
calcRatioTapCorrection(taps; step) | ratio-tap multiplicative correction 1 + (step - neutralStep)·tapStepPercent/100 |
calcRatioTapRange(taps) | (tap_min, tap_max, tap_step) in ratio terms |
calcPhaseTapFraction(m; step) | shared tap fraction f = (step - neutralStep)·voltage_step_increment |
calcPhaseTapAngleRatio(m; step) | (effective_ratio, effective_shift_deg, regulating_vector) |
calcPhaseTapReactance(m, α) | tap-angle-dependent reactance X(α) interpolated between x_min/x_max |
calcPhaseTapTable(m; step) | exact lookup of a tabular row |
For calcPhaseTapAngleRatio, a :symmetrical changer computes α = 2·atand(f/2) with magnitude always 1.0; an :asymmetrical changer maps the regulating vector 1 + f·e^{jψ} through the low-level primitive calcSkewAngleTap, of which the quadrature booster (ψ = 90°) is a special case. A :tabular model resolves ratio and angle by lookup and reconstructs the regulating vector from the stored degrees.
Importer mapping
- DTF builds a
PhaseTapChangerModel(kind = :asymmetrical, winding_connection_angle_deg = skew, ...)and callscalcPhaseTapAngleRatiofor the branchratio/shift. The pure longitudinal case (ψ = 0) keeps the shift at exactly0.0. - MATPOWER keeps the direct
TAP/SHIFTpath, the CGMES "General Case" (raw values), without a model struct; shift unit, shift sign and ratio convention are import options (MATPOWER).
Tap-impedance correction
model.tap_changer_model selects whether a tap step changes the winding ratio alone (ideal, default) or also re-refers the transformer R/X through the tapped winding (impedance_correction, implemented centrally in calcTapCorrectedRX / calcTapImpedanceCorrectionFactor); see Transformer tap-changer model. The switch per path:
| Path | Switch |
|---|---|
| MATPOWER | model.tap_changer_model, ratio form, applied once at import; a file with the mpc.sparlectra.tap_changer_model marker is not corrected again |
| DTF | model.tap_changer_model; applied once at import, or through the typed model when the transformer has a phase model |
typed models (addPIModelTrafo!) | the keyword tap_changer_model; it acts on an asymmetrical (or quadrature) phase model only. A ratio model, a symmetrical or a tabular phase model gets no correction factor. |
| SCF | per transformer, the key tap_changer_model of its tap_changer_models entry, written by the export; model.tap_changer_model does not change it |
| CGMES | not applied; the impedance per step comes from the data (tap tables, xMin/xMax, TapStepImpedance) |
| PowSyBl | not applied; the impedance at the import step comes from the r, x, g, b of that tap changer step, and the state estimation takes the step rows as its table |
In the state estimation, state_estimation.tap_estimation.impedance_correction (auto, off) acts on the analytic correction only, decided per transformer. Per-step data of an imported changer set (CGMES, PowSyBl; tap table rows with r and x, the reactance curve from xMin/xMax, TapStepImpedance factors) always follow the step, and the analytic correction is off for that transformer under both values. A typed model follows the power flow: its x_min/x_max curve or x table follows the step under both values, and the correction factor on R that the power flow applies next to the curve under impedance_correction is taken under auto only. A typed x curve or x table (SCF tap_changer_models, addPIModelTrafo!) counts as a step table like the CGMES tables. Without per-step data auto applies the correction of a typed asymmetrical model built with impedance_correction (Branch.tap_correction), and off keeps the impedance of the start position (see State estimation extensions).
The factor $|1 + f e^{j\psi}|^2$ is defined for the convention reciprocal_from_side of a typed asymmetrical or quadrature changer. A typed model in the convention direct_regulating_vector under impedance_correction gets the same factor, but no physical chain matches it (next section). The SCF reader warns once per such transformer.
One branch or an explicit chain
A transformer with its tap changers is one branch with the complex ratio $t(s)$. An explicit chain (ideal transformer, PI section of the ratio part, auxiliary bus, PI section of the phase part) has the same terminal admittance and gives the same power flow for the cases below.
| Changer kind | Series impedance of the chain | Impedance of the one branch |
|---|---|---|
| ratio changer, ratio table | behind the ratio part | constant |
| symmetrical, linear | before or behind the phase part | constant, or the reactance curve |
| asymmetrical and quadrature (CGMES, nameplate), phase table | behind the additional voltage | constant, the reactance curve, or the table r and x |
asymmetrical and quadrature, typed, reciprocal convention, impedance_correction | before the additional voltage | R and X scaled with abs(1 + f e^{j psi})^2 |
No chain matches the typed direct convention under impedance_correction, or a ratio and an asymmetrical changer on one winding with constant impedance.
Three-winding transformers
A three-winding transformer is a star (T) equivalent with an auxiliary star-point bus: each winding becomes its own PowerTransformerWinding, stamped as a separate branch to the AUX bus (create3WTWindings!, MVA method). Every winding carries its own taps and phase_taps slots; a phase-shifting winding places the regulating vector on its branch to the star point, with the same stamping and ψ interpretation as a two-winding device.
create3WTWindings! accepts an optional phase_tap_side (winding index 1..3, 0 = none) and phase_taps::PhaseTapChangerModel pair, the same 1-based convention as tap_side; phase_tap_side may equal tap_side when a winding carries both a ratio tap and a phase tap:
psc = PhaseTapChangerModel(kind = :asymmetrical, step = 0, lowStep = -8, highStep = 8, neutralStep = 0, winding_connection_angle_deg = 60.0)
w1, w2, w3 = create3WTWindings!(u_kV = [110.0, 20.0, 10.0], sn_MVA = [100.0, 80.0, 20.0], addEx_Side = [tmp1, tmp2, tmp3], sh_deg = [0.0, 0.0, 0.0], tap_side = 1, tap = tapSettings, phase_tap_side = 2, phase_taps = psc)Not implemented: resolving w2.phase_taps into an effective ratio/shift on the AUX-bus branch, and addressing a single 3WT winding from the outer-loop PowerTransformerControl framework.
5. Transformer control (outer loop)
Transformers are regulated within the branch PI model using the complex tap t = τ·e^{jφ} and without auxiliary nodes: τ for voltage control, φ for active-power-flow (PST) control, both together for combined regulation. Loop mechanics, deadbands, limits and the hook interface: Control Framework. Branch-model specific are the complex tap in the PI equivalent and the tap-dependent reactance.
Tap-dependent reactance X(α)
For a PST whose winding carries a typed PhaseTapChangerModel with reactance data, the outer loop couples the series reactance to the tap angle: every accepted phase-tap move also updates the branch x_pu, and the next outer-loop solve re-stamps the Y-bus from it. Mapping from the controller's continuous angle to a reactance:
- formula models (
:symmetrical/:asymmetricalwithx_min = X(0),x_max = X(αmax)):calcPhaseTapReactanceevaluated at the continuous angle; - tabular models: the nearest table row by angle supplies its per-step
x_pu(no interpolation between rows).
The coupling is opt-in per device: a winding without a typed model, a formula model without x_min/x_max, or a tabular model without x_pu values keeps its static reactance (MATPOWER general-case PSTs). A CGMES transformer has no typed model. When its tap table points carry r and x, or its phase tap changer has an xMin/xMax curve, the branch stores the impedance per step (TapStepImpedance), and a tap controller that moves the step sets the impedance of the new step. A CGMES PST without such data keeps its static reactance. The probe that estimates the tap direction perturbs the reactance consistently with the apply step, restores both, and refreshes the branch flows around each probe solve.
Discrete tap behaviour
tap_ratio_new = clamp(tap_ratio ± tap_step, tap_min, tap_max)
phase_shift_deg_new = clamp(phase_shift_deg ± phase_step_deg, phase_min_deg, phase_max_deg)Phase-shift control direction (practical probe)
The sign of a phase-shifter control action is probed on the active model, not hard-coded:
- Read
P_abat the current phase angle. - Move the phase tap one step up (
phase_step_deg, clamped to the range; on a modelled transformer one model step), re-solve, readP_abagain. - The sign of
Delta_P_abgives the direction in whichP_abgrows. - If
P_ab < target, movephiin that direction; otherwise the opposite way.
See examples/others/exp_pst_reactance_coupling.jl.
Controllers
Registration (addPowerTransformerControl! with its full keyword set, master/slave groups via followers, declarative YAML entries) and the controller result surfaces: Control Framework. Branch-model specific is only the inline form, a controller attached while the transformer branch is created:
ctrl = PowerTransformerControl(
trafo = "",
mode = :voltage,
target_bus = "B5",
target_vm_pu = 1.01,
control_ratio = true,
control_phase = false,
)
addPIModelTrafo!(
net = net,
fromBus = "B1",
toBus = "B2",
r_pu = 0.01,
x_pu = 0.08,
b_pu = 0.0,
ratio = 1.0,
shift_deg = 0.0,
status = 1,
controls = [ctrl],
)Scope and limits
One target_bus measurement, one transformer tap as actuator, a target_vm_pu ± deadband objective; parallel transformers on one bus form a master/slave group ("Master/slave groups for parallel transformers" in Control Framework). Not covered: auxiliary transformer nodes, tap variables inside the Newton iteration, participation-factor allocation and tap-limit redistribution within transformer groups.
6. CGMES / ENTSO-E mapping
The typed tap-changer models follow the CGMES data model:
| Sparlectra | CGMES / CIM |
|---|---|
PowerTransformerTaps | RatioTapChanger on a TransformerEnd |
PowerTransformerTaps.voltageIncrement_kV / tapStepPercent | RatioTapChanger.stepVoltageIncrement |
PhaseTapChangerModel(kind = :symmetrical) | PhaseTapChangerSymmetrical |
PhaseTapChangerModel(kind = :asymmetrical) | PhaseTapChangerAsymmetrical |
winding_connection_angle_deg (ψ) | PhaseTapChangerAsymmetrical.windingConnectionAngle |
| quadrature booster (ψ = 90°) | asymmetrical special case (no separate CIM class) |
voltage_step_increment | PhaseTapChangerNonLinear.voltageStepIncrement |
step_phase_shift_increment | PhaseTapChangerLinear.stepPhaseShiftIncrement |
PhaseTapChangerModel(kind = :tabular) | PhaseTapChangerTabular |
TapTablePoint | PhaseTapChangerTablePoint / TapChangerTablePoint |
TapTablePoint.step / ratio / angle_deg / x_pu | TapChangerTablePoint.step / ratio / angle / x |
CGMES recommends exchanging tabular tap data where available instead of recalculating parameters from technology formulas: a :tabular model overrides the formula path, and the formula kinds (:symmetrical, :asymmetrical) are used only without a table. MATPOWER's raw TAP/SHIFT corresponds to the CGMES "General Case".
7. Related documents
- ENTSO-E, Phase Shift Transformers Modelling, CGMES v2.4, 28 May 2014: PST technology classification, tap-angle formulas, reactance-versus-angle characteristics, tabular exchange.
- IEC 61970-301 (CIM base) and the CGMES profiles: the classes in the mapping table above.
- MATPOWER case format documentation: the
TAP/SHIFTbranch columns. - Sparlectra examples (
examples/others/):tap_control_demo_grid.jl,tap_control_schraeg_two_controllers.jl,exp_pst_reactance_coupling.jl; see the examples overview.